The Austrian BAUR PD-SGS handheld partial discharge inspection instrument is used for initial rapid testing of partial discharge activity in live switchgear.
Product Introduction of Austrian BAUR PD-SGS Handheld Partial Discharge Inspection Instrument:
•Quickly identify partial discharge activity in switchgear and cable accessories
•The BAUR handheld partial discharge inspection instrument PD-SGS is used for initial rapid testing of partial discharge activity in live switchgear
•Real-time display of partial discharge both acoustically and digitally
Product Features of Austrian BAUR PD-SGS Handheld Partial Discharge Inspection Instrument:
•Initial rapid condition assessment of switchgear and cable accessories during grid operation
•Ideal for quick inspection of medium and high voltage switchgear
•Built-in 2 sensors:
TEV captures partial discharges on the surface of switchgear
Acoustic sensor captures partial discharges inside switchgear
•Provides higher safety for test personnel - detects safety risks of switchgear before starting work
Technical Parameters of Austrian BAUR PD-SGS Handheld Partial Discharge Inspection Instrument:
| Operating Properties | |
| Ambient Temperature (Operation) | -5°C to +55°C |
| Relative Air Humidity | ≤ 90%, non-condensing |
| Safety and Electromagnetic Compatibility (EMC) | |
| Protection Class | IP 54 |
| Dimensions / Weight | |
| Dimensions (W x H x D) | Approx. 90 x 190 x 65 mm |
| Weight | Approx. 300 g |
| Software & Hardware | |
| Hardware | |
| Display | High-contrast, high-resolution OLED display, 6 display LEDs (partial discharge level) |
| Operating Elements | 2 keys (membrane keyboard) 1 trigger switch |
| Interfaces | Power supply Headphones External acoustic sensor |
| Battery | |
| Power Supply (built-in battery with charger) | Lithium-ion battery 2.2 Ah; DC 3.75 V |
| Battery Life | Approx. 12 h |
| TEV Measurement | |
| Sensor | Capacitive |
| Measurement Range | 0 to 80 dBmV |
| Frequency Range | 20 MHz to 200 MHz |
| Resolution | 1 dB |
| Accuracy | ±1 dB |
| Ultrasonic Measurement | |
| Measurement Range | -6 to +70 dBμV |
| Resolution | 1 dB |
| Accuracy | ±1 dB |