Desktop|中文
Home About Us Products + News Center Technical Articles Messages Contact Us

Product Details

全自动Dielectric Loss Tester-扬州达瑞

Circuit Breaker Switch Characteristic Tester - Yangzhou DARUI Co., Ltd.

Published: 2020-08-15 15:42:47

Views: 2922

Category: Switch Characteristic Tester

Product Description

Circuit Breaker Switch Characteristic TesterCircuit Breaker Switch Characteristic Tester



DARUI Electric recommends for you



1. Time measurement: 12 channels



             Inherent opening (closing) time



             Non-simultaneity within phases for opening (closing)



             Non-simultaneity between phases for opening (closing)



             Bounce time (bounce count) during closing (opening)



2. Test range: 0.01ms~10000ms



3. Accuracy: within 1ms~100ms accuracy 0.1%±2 digits,



             greater than 100ms accuracy 0.5%±2 digits



4. Speed measurement: just opening (just closing) speed



             Average speed over specified time period (travel segment or angle segment)



5. Speed measurement range: 1mm sensor 0.01~25.00m/s,



0.1mm sensor 0.001~2.50m/s,



360° angle sensor 0.01~25.00m/s



6. Travel measurement: moving contact travel (stroke)



             Contact travel (opening distance)



             Overshoot or return travel (over-travel)



7. Sensor measurement range: linear displacement sensor 50mm, resolution: 0.1mm, travel 0.1~50mm



                   Linear displacement sensor 300mm, resolution: 0.1mm, travel 10~300mm (optional)



                   Linear displacement sensor 500mm, resolution: 1mm, travel 10~500mm (optional)



                   360-line sensor: 360°, resolution: 0.25°, travel 1mm~1000mm   



8. Current measurement: displays the maximum current value of the opening (closing) coil



9. Display screen: 320×240 LCD, contrast adjustable



10. Data storage: can store 100 sets of measurement data



11. Printer: high-speed thermal printer



12. Instrument power supply: AC/DC 220V ± 10%; 50Hz ± 2%



13. DC power supply



1) Output voltage: 25~265V continuously adjustable



2) Output current: ≤ 20A (short time)



14. Main unit dimensions: 360×250×140mm



15. Operating environment: -10℃~+50℃



16. Relative humidity: ≤90%



Technical Specifications



Maximum speed: 20m/s, resolution: 0.01m/s; test accuracy: ±1.0% reading ±0.05 ;



Travel test range: 6mm~300mm;



Travel minimum resolution: 0.1mm; test accuracy: ±1.0% reading ±0.1mm;



Time test range: 10ms~15s,



Time resolution: 0.1ms; time test accuracy: ±0.5% reading ±0.2ms;



Minimum action simultaneity difference resolution: 0.1ms; test accuracy: ±0.5% reading ±0.1ms;



Test channels 8: 6 channels for contact time, 1 channel for speed, 1 channel for coil current;



Power supply: AC220V±10%; 50Hz±1Hz;



Operating power output: voltage DC30V~300V adjustable, current 20A, digital program control, continuous working time 3s;



Time Measurement



Speed and Travel Measurement



Opening (closing) time: The opening (closing) time refers to the time from when the switch receives the opening (closing) control signal (coil energized) to when the moving contact and static contact first separate (close).



Intra-phase simultaneity: The difference between the maximum and minimum opening and closing times among contacts of the same phase.



Inter-phase simultaneity: Among phases A, B, and C, the difference between the maximum closing times of each phase is the closing inter-phase simultaneity, and the difference between the minimum opening times is the opening inter-phase simultaneity.



Bounce count: The bounce count refers to the number of times the moving and static contacts separate (close) during the opening (closing) operation.



Bounce time: The bounce time refers to the time from the first separation (or closing) of the moving and static contacts to the final stable separation (or closing).



Contact curve: The opening and closing state of the contacts, and plot the "state-time" curve;



Speed and Travel Measurement



Just opening (closing) speed: The just opening (closing) speed refers to the average speed within a specified time or distance when the moving and static contacts contact. This tester provides many definitions of just opening (closing) speed for various switches.











 


WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio Tester、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com