全自动Dielectric Loss Tester-扬州达瑞

Detailed Information of Current Transformer Secondary Loop Load Tester - Yangzhou Dary Co., Ltd.

Published: 2020-08-12 16:29:59

Views: 2922

Category: High Current Generator Device

Product Description
Detailed Information of Current Transformer Secondary Loop Load Tester

Dary Electric recommends for you



The error existing in the electric energy metering device is the comprehensive error of electric energy metering, which is composed of the error of the electric energy meter, the composite error of the voltage transformer, the composite error of the current transformer, and the metering error caused by the voltage drop of the secondary wire of the voltage transformer. It can be expressed by the following formula:

ε=εw+εTA+εTV+εr

Where εw—Error of electric energy meter %

εTA—Composite error of current transformer %

εTV—Composite error of voltage transformer %

εr—Metering error caused by voltage drop of secondary wire of voltage transformer %

In the electric energy metering circuits of power plants and substations, the outdoor voltage transformer is far from the electric energy meter installed on the distribution panel in the control room, generally about 200 to 400 m. The entire circuit has terminal blocks, switches, fuses, and wires, which inevitably have contact resistance, wire resistance, and distributed parameters, thus there is a certain circuit impedance, resulting in a voltage drop on the secondary circuit between the voltage transformer and the electric energy meter. The voltage drop of the secondary circuit of the voltage transformer includes the total of voltage drops of cables, terminal contact resistance, fuses, intermediate relay contacts, small air switches, etc. The error caused by the secondary voltage drop of the voltage transformer refers to the percentage of the amplitude difference between the secondary terminal voltage of the voltage transformer and the load terminal voltage relative to the actual secondary voltage, as well as the phase difference between the two voltages.





Main Technical Indicators

Environmental Conditions

——Temperature: -5?C~40?C

——Relative Humidity: <95%(25?C)

——Altitude: <2500m

——External Interference: No strong vibration, no strong electromagnetic field



Main Technical Indicators of PT Current Transformer Secondary Loop Load Tester

1). PT Secondary Load Test

——Admittance Measurement Range: 0.1ms—50.0ms

——Admittance Measurement Accuracy:

——Secondary Voltage (50V-120V)

?X=?(2%×X+2%×Y)?2 words

?Y=?(2%×X+2%×Y)?2 words

2 words——Quantization error of the instrument

Note: When the measured value is below 0.2mS, the test voltage should be kept above 50V, and at the same time, pay attention to keep the wire passing through the center of the clamp meter. At this time, the quantization error of the instrument is 5 words

2). Voltage Meter Head: 0.5%



Main Technical Indicators of CT Current Transformer Secondary Loop Load Tester

——Impedance Measurement Range: 0.1Ω—50.0Ω

——Impedance Measurement Accuracy:

?X=?(2%×X+2%×Y)?2 words

?Y=?(2%×X+2%×Y)?2 words

2 words——Quantization error of the instrument

Current Meter Head: 1%




Note: The above information and technical parameters are compiled and released by Yangzhou Dary Electric Co., Ltd.

 
WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio Tester、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us