Fully Automatic High-Efficiency High and Low Voltage Switchgear Power-On Test Bench
Dali Electric recommends
High Voltage Switchgear Test Device, used for factory commissioning and debugging of high and low voltage switchgear manufacturers, and can also be used for substation maintenance to replace the station DC operation power supply and other occasions requiring DC power supply. In power plants, substations, switchgear factories and other units, primary equipment is important, and secondary equipment is also important, because primary and secondary equipment form a whole, and only when both are in good condition can the safety of power production be guaranteed. Secondary equipment refers to the equipment that monitors, controls, regulates, and protects the working condition of primary equipment, and provides operating personnel with working condition or production command signals. Therefore, faults in the secondary circuit often damage or affect the normal operation of electrical equipment. Properly using and managing the electrical equipment of the secondary circuit is an important link to ensure the safety of power production. This test vehicle is designed and produced by our company based on the requirements of secondary circuit testing and trial, starting from the actual needs of users for secondary circuit testing. This product has the characteristics of full functions, small size, beautiful appearance, and easy movement, making it an ideal device for testing various parameters of secondary equipment.
Technical Conditions:
Input Power: Three-phase four-wire AC 380V
Output Voltage and Current:
1. Three-phase AC 0 – 10A output (<100V, adjustable) one group
2. Three-phase AC 100V output (fixed value) one group
3. AC operation voltage output AC 0~400V, at 220V, current less than 10A
4. DC operation voltage output DC 0~260V
5. DC closing power supply output DC 0~300V (rated current 100A, short-time working current 300A) one group
6. Single-phase AC220V output (fixed value, socket form) two groups,
7. Three-phase AC380V output (fixed value, terminal) one group,
8. Dimensions: 560*520*850mm
9. Weight: 45kg
Product Parameters:
| Input Power: | AC380V/32A, one input two outputs, using waterproof socket | ||||||||
| Current Output: | 0~5A (adjustable, with transfer switch controlling KE, LE two types) | ||||||||
| Voltage Output: | AC Output: | 0~520V (adjustable 10A, three-phase four-wire, four groups) | |||||||
| 380V (fixed value, three-phase four-wire one group) | |||||||||
| 220V (fixed value two groups, one on front and one on back panel) | |||||||||
| 110V (fixed value two groups, one on front and one on back panel) | |||||||||
| DC Output: | 0~270V (adjustable, 20A) | ||||||||
| The entire console should have a power factor controller, and the power factor is adjustable, including leading and lagging, adjustable values are 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 1 | |||||||||
| Instrument Display: | Adjustable AC voltage output | ||||||||
| DC adjustable voltage output, and DC current value | |||||||||
| Multifunction meter display, can display current power, power factor, voltage and other values during test instrument circuit. | |||||||||
| Time display value | |||||||||
Operating Instructions:
1. Connect the input power AC380V
2. Connect the AC operation voltage output power line to the voltmeter
3. Check and confirm the wiring is correct, turn on the main power switch 4. Return the voltage regulator to zero, and press the "Close" button,
5. Then press the "Close" button of the AC operation voltage on the panel
6. Slowly adjust the output adjustment knob to raise the voltage to the required value, and observe the voltmeter.
7. After the test, first press the "Open" button of the AC operation voltage on the panel, then press the main "Open" button on the panel. Then, disconnect the main power switch

Note: The above information and technical parameters are compiled and released by Yangzhou Dali Electric Co., Ltd.