I. Functional Features
1. Large screen Chinese display, menu operation, user-friendly interface.
2. Automatic calibration, automatic measurement of group, group transformation, phase sequence switching, and range switching.
3. After inputting the standard turns ratio, it can automatically calculate the relative error.
4. After measurement, the test voltage is automatically cut off.
5. Set data, measurement results are automatically saved, and previous data can be viewed.
6. For measuring on-load transformers, only input the turns ratio.
II. Technical Specifications
1. Turns ratio measurement range: 1-10000
2. Group: 1-12 points
3. Accuracy: 1-1000 0.2 class 1.5 class
4. Power supply: AC220V ±10%, 50HZ
5. Operating ambient temperature: -5℃ ─ 40℃
6. Operating ambient humidity: <85%
7. Dimensions: 430×320×215mm3
8. Weight: 8Kg