I、Overview
According to the new State Power Corporation document (2002) No. 777 "Regulations for Preventive Tests of Power Safety Tools and Equipment", the required methods are used to more scientifically and reasonably complete the power frequency withstand voltage tests for common auxiliary insulation tools such as insulation gloves, insulation boots, and insulation rubber pads.
Auxiliary insulation safety tools refer to those whose insulation strength is not to withstand the working voltage of equipment or lines, but only to strengthen the protective effect of basic insulation safety tools, to prevent contact voltage, step voltage, and leakage current arcs from harming operators. They cannot be used to directly contact live parts of high-voltage equipment. Safety tools in this category include: insulation gloves, insulation boots, etc.
This instrument is mainly used for power frequency withstand voltage tests on safety tools such as insulation gloves and insulation boots, to determine whether these tools meet the conditions of use and ensure the personal safety of workers.
Test Basis
The "Regulations for Preventive Tests of Power Safety Tools and Equipment" issued by the State Power Corporation and implemented on November 7, 2002.
II. Main Functional Features
1. Color display screen, human-machine dialogue operation, easy to operate;
2. Can test 6 specimens simultaneously, improving work efficiency;
3. Automatically print test reports;
4. Parameters can be set for preventive insulation performance tests of other products;
5. The whole device consists of two parts: a high-voltage cabinet and a main unit (control box data processing device);
6. Can perform intelligent preventive insulation performance tests for insulation boots, high-voltage insulation gloves, and low-voltage insulation gloves, with complete items;
7. Parameters can be set for leakage current measurement tests of other products;
8. The test process is controlled by a microcomputer, with automatic voltage increase and decrease;
9. High and low voltage isolation, safe and reliable;
10. Automatic timing at test voltage.
III. Main Technical Specifications
Special electrode: ф2.5mm steel balls
Test voltage: AC 0—30kV
Test current: 0—15mA
Current measurement accuracy: ±1 level (±2 digits)
Voltage measurement accuracy: ±1 level (±5 digits or ±1kV) (manual mode)
**Test quantity: 3 pairs/6 pieces (customizable for more) 6-channel leakage current detection
Power supply: AC220V ±10%